Primer GF-021 , being the most wide-spread and cheapest material, is mostly commonly used for the civil construction objects. Hence the systems based on exactly this material have been developed for protection of the indoor metal structures. If more reliable and long-term protection is required we can offer the system based on the vinyl epoxy primer VINICOR-061.

Standard coating systems for indoor metal structures

primerfire-proof painttop enamel*
descriptionnumber of layers (thickness of coating)grade /brandnumber of layers **(thickness of coating)descriptionnumber of layers (thickness of coating)
GF-021-based coating
GF-021
alkyd
2 layers
40-60 mcm
PLAMCOR-1
or
PLAMCOR-2
1-4 слоя
0,3-1,5 mm

1-4 layers
0,2-1,5 mm
PОLYTON-АК
or
PОLYTON-UR
or
VINICOR-62
1 layer
50-70 mcm
Primer based coatings (improved protection properties)
VINICOR-061
vinyl-epoxy
1 layer
40-60 mcm
PLAMCOR-1
or
PLAMCOR-2
1-4 layers
0,3-1,5 mm

1-4 layers
0,2-1,5 mm
PОLYTON-АК
or
PОLYTON-UR
or
VINICOR-62
1 layer
50-70 mcm

* to ensure aesthetically pleasing appearance or protection from aggressive environment the following top enamels are recommended for use: acrylic POLYTON –AK , polyurethane POLYTON-UR or vinyl-epoxy VINICOR -62;
** thickness of coating depends on the fire-resistance time/ rating and metal thickness.

Fire protection of open-air located objects

The fire-proof paint PLAMCOR-3 is recommended for critical and high-security objects.

Standard coating systems for outdoor metal structures

primerfire-proof painttop enamel*
descriptionnumber of layers (thickness of coating)grade /brandnumber of layers **(thickness of coating)descriptionnumber of layers (thickness of coating)
primer based coatings (improved protection properties)
ISOLEP-primer
epoxy with zinc phosphate
1 layer
60-100 mcm
PLAMCOR-3 1-4 layers
2,0-4,5 mm
PОLYTON-UR (UV) 1 layer
50-70 mcm
Primer –based coating (improved protection properties)
(zinc «cold» galvanizing)
ZINOTAN
polyurethane zinc-rich
1 layer
40-80 mcm
PLAMCOR-3 1-4 layers
2,0-4,5 mm
PОLYTON-UR (UV) 1 layer
50-70 mcm

* to ensure aesthetically pleasing appearance or protection from aggressive environment the following top enamels are recommended for use: acryl-urethane POLYTON-UR(UV);
** thickness of coating depends on the fire-resistance time/ rating and metal thickness.